Exhibit 4.8.6 - Electronic Catalogue (1,3,4,5) - 42CV



 
 

 


Carrier China
 
Carrier is affiliated to United Technologies. United Technologies ranks 120 in world’s 500 tops (2005), its business extends to architectural industry and aerospace industry around the world.

In 1902, Professor Carrier invented first set of scientific air-conditioning system. Since then, carrier’s complete series products and system resolution have become first choice of many world-renowned buildings.

Carrier’s sales revenue reaches 14.6 billion US dollars, leading in the whole industry. Its distributors’ network covers over 170 countries. Carrier is now world’s biggest HVAC manufacturer.

Carrier China has 13 companies, more than 40 sales service offices with over 2,500 employees.

As the world-class factory, Carrier China has several advanced production lines of units and compressors, covering main units of commercial and residential central air-conditioning systems and air terminal products. The various products can meet diversifying demands from different customers.

Contents

Type No.
 
1
Air Flow
  1
Unit Characteristics
 
2
Technical Specification
 
4
External Dimensions
 
5
Performance Data
 
6
Purchase Guideline
 
16
Fan Performance
 
18
Electrical Data
 
19
     
Acoustic Noise Test
 
20
Supply Line
  20
     
Installation and Maintenance Instructions
  
21
 
 
 

 

Type No.

 
•  Page1, 2
Product Series
42fan coil unit
•  Page 3, 4
Type Letter Label
CLCrouching exposed fan coil unit
VLVertical exposed fan coil unit
VM: Vertical concealed fan coil unit
VP: Vertical concealed fan coil unit (high static pressure type)
CW: High static pressure type fan coil unit
CHhigh static pressure type fan coil unit (combined coil)
•  Page 5, 6, 7
Unit specification (air flow= unit specification X I70m3/h)
002: 340m3/h
003: 510m3/h
•  Page8
Unit connection direction
L: Left
R: Right

Air Flow
 
3402040m3/h

 
 
1

 

Unit Characteristics
 
Carrier fan coil units are used for semi-concentrated air conditioning systems. Due to load varying characteristics, advanced design, full product range and superior performance, they are widely used in hotels, apartments, office buildings, etc.

•  Eight Types: with air flow from 3402550m3/hcooling capacity from 192011510W
•  Vertical type and crouching type
•  Exposed installation and concealed installation
•  Left or right connector
• Single or combined coils (single or double line water supply and return system)

Low floor occupying
 
The fan coil unit is very thin. It is possible to be installed in any place.

Fast installation
 
One person can install the unit because of its compact size, excellent balance and easy cable connection.
 
Beautiful outlook
 
Balanced structure and smooth outline
 
High efficiency
 
Copper tubes are used for high heat transfer efficiency. Hyperbolic slit fin type heat exchanger and mechanical pipe expanding ensure close contact between copper tubes and fins.
 
Electricity saving
 
Three adjustable fan speeds with permanent capacitor motor make it possible to save electricity.

Easy maintenance
 
Concentrated heating and cooling units with high capacity and easy adjusting functions keep a low maintenance expense. As equipped with condensed water tray, drainage devices and self-cooling motor, it is easy for maintenance with least failures.
 
Low noise
 
The reasonable fan design together with low motor rotational speed and noise absorbent and heat insulating materials, 42C/V Series fan coil units create a quiet and comfortable working and living environment.

Note: left and right are judged when facing the unit.
 
 
 
2

 

 
Full Range           Excellent Performance
   
 
   
 
42CE Crouching Concealed Type (See detail in 42CE sample
   
 
This type is high compact, and can be hidden in ceiling. It's an ideal product for hotel, apartment, office building, etc.
   
 
   
 
42VM Vertical concealed installation type
   
 
42VP Concealed installation, high static pressure fan coil unit
   
 
Special designed types of high stand, edge lining and stand 2VM42VPsuitable for outside window installation with only a thickness of 232mm.  42VM and VP types are ideal for in-wall installation or decoration board with a notch. There are 8 specifications for each of these two types with sound performance and easy maintenance.
   
 
   
 
42CL Crouching Exposed Installation Type
   
 
It is ideal for hosting in ceilings of all buildings without floor occupying, and particularly appropriate for renovation of old buildings with low pipeline consumption and low cost. Outer shell is protected by durable stoving varnish with colors matching indoor decorations.
   
 
   
 
42VL Vertical Exposed Installation Type
   
  
Beautiful appearance of this unit can be directly placed on the floor of indoors, with colors matching indoor decorations. Removable entire assembling panel facilitates periodic inside unit inspection. Equipped with speed adjustment switch.
 
 
3

 

Technical Specification

CL/VL/VM/VP
Type
002
003
004
006
008
010
012
Rated air flow
m3/h
High Speed
340
510
680
1020
1360
1700
2040
Medium Speed
230
350
470
750
940
1200
1500
Low Speed
150
230
320
480
640
800
960
Cooling Capacity W
-
1920
2790
3840
5230
7680
8720
10470
Heat Capacity W
-
3260
4650
6400
8720
12790
14530
17450
Input Power W
VL/VM/CL
31
35
50
87
100
160
174
VP
35
77
87
134
174
210
268
Noise Value dB (A)
VL/VM/CL
37
39
39
47
43
47
50
VP
40
42
42.5
49.5
47
50
53
Water Volume l/min
-
5.5
8
11
15
22
25
30
Water Pressure Drop kPa
-
8
17
18
27
36
45
22
Air conditioner fan
Form
Centrifugal, multi-blade forward fan
Quantity
1
1
2
2
4
4
4
Motor
Form
Permanent capacitor motor
Quantity
1
1
1
1
2
2
2
Form
copper tubes, Hyperbolic slit fins
coil
working pressure
1.5MPa
connecting pipe
supply and return water
3/4" internal thread 3/4" FPT
condensation water
3/4" external thread 3/4" MPT
net weight
VL
19
21
23.5
28
38
38
40
CL
19.5
21.5
24.5
30
41
41
50
VM/VP
14
15
18
22
32
32
39
optional accessories
VL
 
CL/VM/VP
     
Temperature control switch
     

Note:
1. Cooling capacity value measured is when entering water temperature is 7 ° C, inlet and outlet temperature difference 5 ° C, air DB = 27 ° C and WB = 19.5 ° C. Heating capacity valued measured is when hot  entering water temperature is 60°C and air DB = 21°C.
2. Rated air flow, Cooling Capacity and heat capacity when residual pressures of VL, CL, VM are 0 and when residual pressure of VP is 30.
3. Performance data in the chart is high speed air flow. Refer to noise test method at page 20.

 
4

 

External Dimension

42VL
 
 
42VL
Dimensions
A
B
C
002
924
549
524
003
1044
669
644
004
1164
789
764
006
1404
1029
1004
008
1764
1389
1364
010
1764
1389
1364
012
2244
1869
1844
 
42CL
 
 
42CL
Dimensions
A
B
002
924
549
003
1044
669
004
1164
789
006
1404
1029
008
1764
1389
010
1764
1389
012
2244
1869
 
42VM/VP
 
42
Dimensions
VM/VP
A
B
C
D
E
002
574
524
549
360
10
003
694
644
669
4480
12
004
814
764
789
600
14
006
1054
1004
1029
840
18
008
1414
1364
1389
1200
24
010
1414
1364
1389
1200
24
012
1894
1844
1869
1688
32
 
 
5

 

Performance Data

Cooling Capacity
(W)   
 
Inlet
 
Water
 
 
Water
Water
Pressure
Inlet Air Temp
Type
Temp
Volume
Drop
17.0WB
18.0WB
19.0WB
 
°C
l/min
kPa
24.0DB
25.0DB
26.0DB
26.0DB
27.0DB
       
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
002
5
4
5
1580
1270
1710
1280
1710
1380
1840
1290
1840
1380
5.5
8
1840
1420
2000
1430
2000
1540
2150
1440
2150
1550
7
13
2020
1510
2200
1540
2200
1650
2360
1560
2360
1660
8.5
17
2160
1580
2350
1620
2350
1720
2520
1640
2520
1740
6
4
5
1440
1220
1650
1230
1580
1330
1710
1230
1710
1340
5.5
8
1690
1350
1840
1360
1840
1470
2000
1380
2000
1480
7
13
1860
1430
2020
1450
2020
560
2200
1480
2200
1580
8.5
17
1990
1490
2160
1520
2160
1630
2350
1550
2350
1650
7
4
5
1310
1170
1440
1170
1440
1280
1580
1190
1580
1280
5.5
8
1540
1280
1690
1290
1690
1400
1840
1310
1840
1420
7
13
1690
1350
1860
1370
1680
1480
2020
1400
2020
1500
8.5
17
1800
1400
1990
1430
1990
1540
2160
1450
2160
1560
8
4
5
1190
1130
1310
1130
1310
1230
1440
1140
1440
1230
5.5
8
1380
1210
1540
1220
1540
1330
1690
1240
1690
1350
7
13
1520
1260
1690
1290
1690
1400
1860
1310
1860
1420
8.5
17
1630
1300
1800
1340
1800
1440
1990
1370
1990
1480
9
4
5
1050
1050
1190
1090
1190
1190
1310
1090
1310
1200
5.5
8
1230
1130
1380
1160
1380
1260
1540
1170
1540
1280
7
13
1350
1170
1520
1210
1520
1300
1690
1230
1690
1310
8.5
17
1440
1200
1630
1240
1630
1340
1800
1280
1800
1340
10
4
5
920
920
1050
1050
1050
1050
1190
1060
1190
1150
5.5
8
1070
1060
1230
1000
1230
1190
1380
1120
1380
1210
7
13
1190
1080
1350
1110
1350
1220
1520
1150
1520
1260
8.5
17
1270
1090
1440
1150
1440
1240
1630
1190
1630
1280
003
5
6
10
2380
1910
2580
1920
2580
2070
2780
1930
2780
2080
8
17
2670
2060
2910
2080
2910
2230
3130
2110
3130
2260
10
26
2880
2150
3130
2190
3130
2340
3360
2210
3360
2440
12
35
3040
2220
3280
2260
3280
3350
3540
2290
3540
2240
6
6
10
1990
1740
2190
1770
2190
1910
2280
1780
2380
1920
8
17
2230
1850
2450
1870
2450
2020
2670
1910
2670
2050
10
26
2410
1910
2640
1950
2640
2110
2580
1990
2880
2140
12
35
2520
1950
2780
2000
2780
2150
3040
2050
3040
2200
7
6
10
1790
1670
1990
1690
1990
1840
2190
1710
2190
1850
8
17
2010
1740
2230
1780
2230
1920
2450
1800
2450
1950
10
26
2160
1790
2410
1840
2410
1980
2640
1870
2640
2010
12
35
2280
1830
2520
1870
2520
2020
2780
1920
2780
2070
8
6
10
1590
1590
1790
1620
1790
1770
1990
1630
1990
1780
8
17
2010
1740
2230
1780
2230
1920
2450
1800
2450
1950
10
26
2160
1790
2410
1840
2410
1980
2640
1870
2640
2010
12
35
2280
1830
2520
1870
2520
2020
2780
1920
2780
2070
9
6
10
1590
1590
1790
1620
1790
1770
1990
1630
1990
1780
8
17
1790
1640
2010
1670
2010
1810
2230
1710
2230
1850
10
26
1920
1660
2160
1720
2160
1860
2410
1760
2410
1900
12
35
2020
1690
2280
1740
2280
1880
2520
1800
2520
1930
10
6
10
1400
1400
1590
1550
1590
1590
1790
1560
1790
1710
8
17
1560
1540
1790
1570
1790
1710
2010
1600
2010
1740
10
26
1690
1540
1920
1590
14920
1730
2160
1640
2160
1780
12
35
1770
1550
2020
1600
2020
1740
2280
1670
2280
1800

Note:
1. DB - Dry bulb temperature ° C, WB - wet bulb temperature ° C.
 
2. The displayed cooling capacities in above chart are those at high-speed. Cooling capacities at medium speed and low speed should be values in above chart multiplied by the speed correction factors VS. 
 
 
6

 
 
Performance Data
 
Cooling Capacity
(W)   
Type
Inlet Water
Temp
°C
Water
Volume
l/min
Water
Pressure
Drop
kPa
Inlet Air Temp
19.5WB
20.0WB
21.0WB
22.0WB
27.0DB
27.0DB
28.0DB
26.0DB
27.0DB
30.0DB
     
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
002
5
4
5
1910
1340
1970
1290
1970
1380
2110
1300
2110
1380
2230
1380
5.5
8
2220
1500
2300
1540
2300
1560
2450
1470
2450
1570
2610
1570
7
13
2450
1620
2540
1570
2540
1670
2700
1580
2700
1690
2870
1700
8.5
17
2620
1700
2710
1650
2710
1770
2880
1670
2880
1780
3070
1790
6
4
5
1780
1290
1840
1240
1840
1340
1970
1240
1970
1340
2110
1340
5.5
8
2070
1440
2150
1400
2150
1490
2300
1410
2300
1500
2450
1510
7
13
2280
1540
2360
1500
2360
1600
2540
1510
2540
1620
2700
1620
8.5
17
2430
1620
2520
1570
2520
1670
2710
1590
2710
1690
2880
1710
7
4
5
1640
1240
1710
1200
1710
1290
1840
1200
1840
1290
1970
1290
5.5
8
1290
1370
2000
1330
2000
1430
2150
1340
2150
1430
2300
1440
7
13
2120
1470
2200
1420
2200
1520
2360
1440
2360
1540
2540
1550
8.5
17
2260
1520
2350
1490
2350
1580
2520
1510
2520
1600
2710
1630
8
4
5
1510
1190
1580
1150
1580
1240
1710
1150
1710
1240
1840
1240
5.5
8
1770
1300
1840
1270
1840
1360
2000
1280
2000
1370
2150
1380
7
13
1940
1380
2020
1340
2020
1440
2200
1360
2200
1450
2360
1480
8.5
17
2070
143
2160
1400
2160
1500
2350
1420
2350
1520
2520
1550
9
4
5
1380
1150
1440
1100
1440
1200
1580
1100
1580
1200
1710
1200
5.5
8
1620
1230
1690
1200
1690
1290
1840
1210
1840
1300
2000
1310
7
13
1780
1300
1860
1270
1860
1360
2020
1290
2020
1380
2200
1400
8.5
17
1900
1350
1990
1310
1990
1410
2160
1340
2160
1430
2350
1450
10
4
5
1240
1100
1310
1060
1310
1150
1440
1060
1440
1150
1580
1150
5.5
8
1450
1170
1540
1130
1540
1230
1690
1150
1690
1240
1840
1260
7
13
1600
1220
1690
1190
1690
1280
1860
1210
1860
1300
2020
1330
8.5
17
1710
1260
1800
1220
1800
1310
1990
1260
1990
1350
2160
1370
003
5
6
10
2880
2010
2980
1940
2980
2080
3170
1950
3170
2080
3380
2080
8
17
3230
2190
3350
2120
3350
2270
3570
2130
3570
2280
3790
2280
10
26
3490
2300
3610
2230
3610
2380
3850
2260
3850
2400
4080
2410
12
35
3660
2380
3790
2310
3790
2470
4050
2340
4050
2490
4290
2500
6
6
10
2690
1930
2780
1860
2780
2000
2980
1870
2980
2010
3170
2010
8
17
3010
2080
3130
2020
3130
2160
3350
2040
3350
2170
3570
2190
10
26
3240
2190
3360
2130
3360
2270
3610
2150
3610
2290
3850
2300
12
35
3410
2260
3540
2200
3540
2350
3790
2230
3790
2370
4050
2400
7
6
10
2490
1860
2580
1790
2580
1930
2780
1800
2780
1930
2980
1940
8
17
2790
1990
2910
1930
2910
2070
3130
1940
3130
2080
3350
2090
10
26
3000
2070
3130
2010
3130
2160
3360
2050
3360
2190
3610
2200
12
35
3160
2140
3280
2080
3280
2220
3540
2120
3540
2260
3790
2280
8
6
10
2290
1780
2380
1720
2380
1850
2580
1720
2580
1860
2780
1860
8
17
2570
1880
2670
1830
2670
1970
2910
1850
2910
1990
3130
2000
10
26
2770
1970
2880
1910
2880
2050
3130
19440
3130
2080
3360
2090
12
35
2910
2010
3040
1970
3040
2110
3270
2000
3280
2140
3540
2160
9
6
10
2080
1710
2190
1640
2190
1780
2380
1650
2380
1790
2580
1790
8
17
2350
1790
2450
1730
2450
1870
2670
1760
2670
1900
2910
1910
10
26
2520
1850
2640
1800
2640
1930
2880
1830
2880
1970
3130
1990
12
35
2650
1880
2780
1840
2780
1980
3040
1880
3040
2010
3280
2050
10
6
10
1880
1640
1990
1570
1990
1710
2190
1580
2190
1720
2380
1720
8
17
2120
1700
2230
1640
2230
1780
2450
1660
2450
1800
2670
1810
10
26
2280
1730
2410
1690
2410
1810
2640
1720
2640
1850
2880
1880
12
35
2400
1760
2520
1720
2520
1850
2780
1770
2780
1990
3040
1930

Speed correction factor VS

Type
Medium Speed
Low Speed
Total Heat
Sensible Heat
Total Heat
Sensible Heat
002
0.85
0.83
0.70
0.66
003
0.86
0.84
0.71
0.67
 
 
7

 

Performance Data

Cooling Capacity
(W)   
Type
Inlet Water Temp
°C
Water Volume
l/min
Water Pressure Drop kPa
Inlet Air Temp
17.0WB
18.0WB
19.0WB
24.0DB
25.0DB
226.0DB
26.0DB
27.0DB
     
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
004
5
8
13
3190
2570
3450
2590
3450
2790
3920
2610
3720
2800
11
18
3690
2840
3990
2870
3990
3080
4300
2900
4300
3110
14
20
4020
3010
4360
3060
4360
3280
4800
3090
4800
3310
17
31
4280
3140
4630
3190
4630
3410
4990
3230
4990
3450
6
8
13
2620
2480
3190
2490
3190
2700
3450
2500
3540
2700
11
18
3270
2700
3690
2730
3690
2940
3990
2770
3990
2970
14
20
3690
2850
4020
2900
4020
3120
4360
2940
4360
3150
17
31
3920
2950
4280
3010
4280
3230
4630
3060
4630
3280
7
8
13
2650
2370
2920
2400
2920
2590
3190
2410
3190
2610
11
18
3070
2560
3370
2590
3370
2800
3690
2630
3690
2840
14
20
3360
2670
3690
2730
3690
2940
4020
2780
4020
2990
17
31
3560
2770
3920
2730
3920
3040
4280
2880
4280
3090
8
8
13
2380
2280
2650
2300
2650
2500
2920
2310
2920
2510
11
18
2770
2420
3070
2470
3070
2660
3370
2500
3370
2700
14
20
3020
2510
3360
2570
3360
2780
3690
2630
3690
2830
17
31
3210
2570
3560
2650
3560
2850
3920
2710
3920
2920
9
8
13
2130
2130
2380
2210
2380
2380
2650
2220
2650
2420
11
18
2450
2270
2770
2330
2770
2520
3070
2360
3070
2560
14
20
2690
2340
3020
2410
3020
2610
3360
2470
3360
2660
17
31
2850
2370
3210
2470
3210
2660
3560
2540
3560
2730
10
8
13
1860
1860
2130
2130
2130
2130
2380
2140
2380
2340
11
18
2150
2130
2450
2190
2450
2380
2770
2230
2770
2430
14
20
2350
2150
2690
2230
2690
2430
3020
2300
3020
2490
17
31
2490
2170
2850
2270
2850
2470
3210
2360
3210
2550
006
5
12
18
4630
3690
5010
3710
5010
4000
5400
3740
5400
4010
15
27
5020
3870
5440
3920
5440
4310
5860
3950
5860
4230
18
37
5310
4000
5760
4060
5760
4350
6200
4110
6200
4400
21
57
5540
4110
5000
4150
5000
4470
6470
4220
6470
4510
6
12
18
4240
3520
4630
3560
4630
3840
5010
3580
5010
3860
15
27
4610
3680
5020
3730
5020
4010
5440
3770
5440
4050
18
37
4870
3890
5310
3850
5310
4140
5760
3910
5760
4190
21
57
5080
3870
5540
3940
5540
4230
6000
4000
6000
4290
7
12
18
3860
3370
4240
3410
4240
3690
4630
3430
4630
3710
15
27
4190
3490
4610
3540
4610
3830
5020
3590
5020
3860
18
37
4430
3570
4870
3640
4870
3920
5310
3700
5310
3980
21
57
4620
3630
5080
3710
5080
3990
5540
3780
5540
4060
8
12
18
3480
3220
3860
3260
3860
3540
4240
3280
4240
3560
15
27
3770
3290
4190
3350
4190
3630
4610
3410
4610
3680
18
37
3990
3350
4430
3430
4430
3700
4870
3500
4870
3770
21
57
4150
3380
4620
3480
4620
3760
5080
3560
5080
3830
9
12
18
3080
3070
3480
3110
3480
3400
3860
3140
3860
3420
15
27
3350
3110
3770
3160
3770
3440
4190
3220
4190
3490
18
37
3550
3130
3990
3210
3990
3480
4430
3290
4430
3550
21
57
3700
3140
4150
3240
4150
3510
4620
3340
4620
3590
10
12
18
2700
2700
3080
2970
3080
3080
3480
3000
3480
3280
15
27
2930
2910
3350
2980
3350
3240
3770
3050
3770
3300
18
37
3110
2960
3550
2990
3550
3260
3990
3080
3990
3340
21
57
3230
2980
3700
3010
3700
3260
4150
3110
4150
3360

Note:
1. DB - Dry bulb temperature ° C, WB - wet bulb temperature ° C.
 
2. The displayed cooling capacities in above chart are those at high-speed. Cooling capacities at medium speed and low speed should be values in above chart multiplied by the speed correction factors VS. 
 
 
8

 

Performance Data

Cooling Capacity
(W)   
Type
Inlet Water Temp
°C
Water Volume
l/min
Water Pressure Drop kPa
Inlet Air Temp
19.5WB
20.0WB
21.0WB
22.0WB
27.0DB
27.0DB
28.0DB
26.0DB
27.0DB
30.0DB
     
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
004
5
8
13
3850
2710
3980
2620
3980
2800
4240
2630
4240
2810
4510
2800
11
18
4450
3010
4610
2920
4610
3130
4910
2940
4910
3140
5220
3150
14
20
4860
3220
5040
3130
5040
3340
5370
3150
5370
3360
5710
3370
17
31
5160
3360
5350
3270
5350
3490
5700
3300
5700
3510
6060
3540
6
8
13
3580
2610
3720
2510
3720
2710
3980
2502
3980
2710
4240
2710
11
18
4140
2880
4300
2790
4300
2990
4610
2810
4610
3010
4910
3020
14
20
4540
3060
4800
2980
4700
3170
5040
3000
5040
3210
5370
3220
17
31
4810
3190
4990
3100
4990
3310
5350
3140
5350
3350
5700
3370
7
8
13
3310
2510
3450
2420
3450
2610
3720
2430
3720
2620
3980
2620
11
18
3840
2740
3390
2660
3990
2860
4300
2690
4300
2870
4610
2900
14
20
4200
2910
4360
2830
4360
3020
4800
2860
4800
3060
5040
3080
17
31
4450
3010
4630
2940
4630
3140
4990
2980
4990
3170
5350
3210
8
8
13
3060
2420
3190
2330
3190
2510
3450
2340
3450
2520
3720
2520
11
18
3540
2620
3690
2540
3690
2720
3990
2560
3990
2741
4300
2770
14
20
3860
2740
4020
2670
4020
2870
4360
2710
4360
2910
4700
2930
17
31
4090
2840
4280
2770
4280
2970
4630
2810
4630
3010
4990
3050
9
8
13
2790
2330
2920
2230
2920
2460
3190
2240
3190
2430
3450
2430
11
18
3220
2480
3370
2410
3370
2590
3690
2430
3690
2620
3990
2640
14
20
3520
2590
3690
2510
3690
2710
4020
2560
4020
2760
4360
2780
17
31
3740
2660
3920
2611
3920
2760
4280
2650
4280
2840
4630
2880
10
8
13
2520
2240
2650
2150
2650
2340
2920
2160
2920
2340
3190
2350
11
18
2920
2350
3070
2270
3070
2470
3370
2310
3370
2490
3690
2510
14
20
3190
2430
3360
2360
3360
2550
3690
2420
3690
2590
4020
2640
17
31
3380
2490
3560
2430
3560
2620
3920
2490
3920
2670
4280
2720
006
5
12
18
5590
3770
5790
3760
5790
4020
6180
3780
6180
4040
6560
4040
15
27
6070
4110
6280
3990
6280
4260
6700
4010
6700
4280
7120
4290
18
37
6420
4280
6640
4150
6640
4430
7090
4190
7090
4450
7540
4480
21
57
6700
4400
6920
4270
6920
4550
7390
4310
7390
4580
7850
4610
6
12
18
5210
3730
5400
3610
5400
3870
5790
3630
5790
3880
6180
3880
15
27
5650
3930
5860
3800
5860
4080
6280
3840
6280
4110
6700
4120
18
37
5980
4070
6200
3950
6200
4220
6640
3990
6640
4260
7090
4280
21
57
6230
4180
6470
4060
6470
4340
6920
4110
6920
4370
7390
4410
7
12
18
4830
3580
5010
3450
5010
3720
5400
3480
5400
3730
5790
3740
15
27
5230
3740
5440
3630
5440
3900
5860
3660
5860
3920
6280
3940
18
37
5540
3860
5760
3760
5760
4020
6200
3790
6200
4060
6640
4090
21
57
55770
3950
6000
3850
6000
4120
6470
3900
6470
4160
6920
4200
8
12
18
4430
3430
4630
3310
4630
3470
5010
3330
5010
3590
6400
3590
15
27
4810
3560
5020
3450
5020
3720
5440
3490
5440
3740
5860
3770
18
37
5090
36960
5310
3560
5310
38910
5760
3610
5760
3860
6200
3900
21
57
5310
3730
5540
3630
5540
39890
6000
3690
6000
3940
6470
3990
9
12
18
4050
3290
4240
3160
4240
3430
4630
3190
4630
3440
5010
3450
15
27
4400
3380
4610
3280
4610
3540
5020
3310
5020
3570
6440
3610
18
37
4650
3450
4870
3420
4870
3620
5310
3410
5310
3660
5760
3710
21
57
4850
3500
5080
340
5080
3680
5540
3480
5540
3730
6000
3780
10
12
18
3660
3150
3860
3020
3860
3290
4240
3060
4240
3310
4630
3330
15
27
3980
3200
4190
3110
4190
3360
4610
3150
4610
3400
5020
3430
18
37
4210
3240
4430
3150
4430
3410
4870
3220
4870
3470
5310
3510
21
57
4380
3280
4620
3200
4620
3440
5080
3270
5080
3510
5540
3580

Speed correction factor VS

Type
Medium Speed
Low Speed
Total Heat
Sensible Heat
Total Heat
Sensible Heat
004
0.87
0.85
0.74
0.70
006
0.89
0.87
0.74
0.70
 
 
9

 

Performance Data

Cooling Capacity
(W)   
Type
Inlet
Water
Temp
°C
Water
Volume
l/min
Water
Pressure
Drop
kPa
Inlet Air Temp
17.0WB
18.0WB
19.0WB
24.0DB
225.0DB
226.0DB
226.0DB
27.0DB
     
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
008
5
16
20
6590
5230
7140
5280
7140
5690
7700
5310
7700
5710
22
36
7370
5610
7980
5680
7980
6090
8590
5730
8590
6140
28
55
7870
5830
8520
5920
8520
6340
9190
6000
9190
6410
34
79
8220
5960
8910
6080
8910
6500
9590
6160
6590
6580
6
16
20
6050
5010
6590
5060
6590
5470
7140
5090
7140
5490
22
36
6760
5300
7370
5380
7370
5800
7980
5450
7980
5860
28
55
7210
5490
7870
590
7870
6000
8520
5690
8520
6080
34
79
7540
5610
8220
5730
8220
6140
8910
5830
8910
6230
7
16
20
5500
4790
6050
4840
6050
5250
6590
4880
6590
5270
22
36
6140
5010
6760
5110
6760
5500
7370
5190
7370
5570
28
55
6560
5150
7210
5270
7210
5660
7870
5370
7870
5760
34
79
6850
5250
7540
5370
7540
5770
8220
5490
8220
5880
8
16
20
4940
4570
5500
4620
5500
5020
6050
4660
6050
5060
22
36
5520
4720
6140
4810
6140
5210
6760
4910
6760
5290
28
55
5910
4800
6560
4940
6560
5330
7210
5050
7210
5430
34
79
6160
4860
6850
5010
6850
5400
7540
5150
7540
5520
9
16
20
4400
4360
4940
4420
4940
4810
5500
4470
5500
4850
22
36
4910
4420
5520
4520
5520
4910
6140
4630
6140
5000
28
55
5250
4450
5910
4610
5910
4980
6560
4730
6560
5110
34
79
5480
4480
6160
4650
6160
5020
6850
4800
6850
5160
10
16
20
3850
3850
4400
4210
4400
4400
4940
4260
4940
4650
22
36
4300
4010
4910
4230
4910
4610
5520
4350
5520
4710
28
55
4590
4080
5250
4270
5250
4620
5910
4410
5910
4770
34
79
4790
4090
5480
4280
5480
4630
6160
4450
6160
4790
010
5
19
28
7820
6200
8470
62660
8470
6750
9130
6300
9130
6770
25
45
8370
6370
9060
6450
9060
6910
9750
6500
9750
6970
31
67
8700
6440
9420
6540
98420
7010
10160
6630
10160
7090
37
90
8740
6480
9690
6610
9690
7060
10430
6690
10430
7150
6
19
28
7180
5940
7820
6000
7820
6490
8470
6040
8470
6510
25
45
7680
6020
8370
6110
8370
6590
9060
6190
9060
6650
31
67
7970
6070
8700
6180
8700
6630
9420
6290
9420
6720
37
90
8200
6100
8930
6230
8930
66670
99690
6340
9690
6770
7
19
28
6520
5680
7170
5740
7170
6220
7810
5780
7810
6250
25
45
6970
5700
7670
5800
7670
6250
8360
5890
8360
6320
31
67
7240
5750
7960
5820
7960
6300
8690
5930
8690
6360
37
90
7430
5790
8180
5840
8180
6320
8920
5920
8920
6380
8
19
38
5860
5420
6520
5480
6520
5950
7170
5530
5050
6000
25
45
6270
5460
6970
5520
6970
5980
7680
5570
7680
6040
31
67
6530
5480
7250
5560
7250
6000
7970
5590
7970
6080
37
90
6700
5500
7450
5580
7450
6020
8200
5610
7200
6100
9
19
38
4760
4720
5350
4790
5350
5210
5960
4840
5960
5250
25
45
5580
5020
6270
5130
6270
5580
6980
5260
6980
5680
31
67
5800
5040
6530
5150
6530
5600
7250
5280
7250
5700
37
90
5960
5050
66700
5160
6700
5620
7450
5300
7450
5710
10
19
38
4570
4380
5220
4600
5220
4960
5860
4770
5860
5120
25
45
4880
4410
5570
4620
5570
5000
6260
4800
6260
5160
31
67
5080
4430
5810
4640
5810
5020
66540
4820
6540
5180
37
90
5200
4440
5960
4650
5960
5030
6700
4840
6700
5200

Note:
1. DB - Dry bulb temperature ° C, WB - wet bulb temperature ° C.
 
2. The displayed cooling capacities in above chart are those at high-speed. Cooling capacities at medium speed and low speed should be values in above chart multiplied by the speed correction factors VS. 
 
 
10

 

Performance Data

Cooling Capacity
(W)   
Type
Inlet
Water
Temp
°C
Water
Volume
l/min
Water
Pressure
Drop
kPa
 
Inlet Air Temp
 
19.5WB
20.0WB
21.0WB
22.0WB
27.0DB
27.0DB
28.0DB
26.0DB
27.0DB
30.0DB
     
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
008
5
16
20
7970
5540
8250
5350
8250
5730
5790
5537
8790
5350
9340
5750
22
36
8910
5970
9210
5790
9210
6190
980
5830
9830
6210
10440
6230
28
55
9510
6230
9840
6060
9840
6470
10500
6120
10500
6540
11150
6550
34
79
9930
6410
10280
6250
10280
6650
10970
6320
10970
6710
11650
6750
6
16
20
7420
5300
7700
5130
7700
5510
8250
5150
7250
5520
8790
5540
22
36
8290
5690
8590
5510
8590
5910
9210
5570
9210
5940
9830
5980
28
55
8850
5920
9190
5760
9190
6150
9840
5830
9840
6210
10500
6250
34
79
9250
6070
9590
5920
9590
6320
10280
6000
10280
6380
10970
6430
7
16
20
6870
5090
7140
4920
7140
5290
7700
4940
7700
5310
8250
5333
22
36
6780
5410
7980
5250
7980
5630
8590
5300
8590
5680
9210
5710
28
55
8200
5610
8520
5450
8520
5840
9190
5540
9190
5910
9840
5950
34
79
8560
5730
8910
5590
8910
5980
9590
5690
9590
60660
10280
6120
8
16
20
6320
4880
6590
4710
6590
5080
7140
4730
7140
5110
7700
5120
22
36
7060
5130
7370
4980
7370
5350
7980
5050
7980
5410
8590
5450
28
55
7550
5290
7870
5150
7870
5520
8520
5230
8520
5610
9190
5660
34
79
7890
5400
8220
5270
8220
5630
8910
5360
8910
5720
9590
5800
9
16
20
5770
4980
6050
4500
6050
4870
6590
4540
6590
4900
7140
4920
22
36
6440
4960
6760
4710
6760
5080
7370
4780
7370
5140
7980
5200
28
55
6880
4980
7210
4850
72101
5210
7870
4940
7870
5290
8520
5370
34
79
7200
5050
7540
4930
7540
5290
8220
5050
8220
5400
8910
5490
10
16
20
5220
4480
5500
4300
5500
4680
6050
4340
6050
4700
6590
4720
22
36
5840
4580
6140
4440
6140
4800
6760
4520
6760
4870
7370
4930
28
55
6230
4650
6560
4540
6560
4880
7210
4640
7210
4990
7870
5070
34
79
6510
4700
6850
4590
6850
4940
7540
4720
7540
5060
8220
5160

Speed correction factor VS

Type
Medium Speed
Low Speed
Total Heat
Sensible Heat
Total Heat
Sensible Heat
008
0.86
0.84
0.73
0.69
010
0.86
0.84
0.73
0.69

 
11

 

Performance Data

Cooling Capacity
(W)   
Type
Inlet
Water
Temp
°C
Water
Volume
l/min
Water
Pressure
Drop
kPa
Inlet Air Temp
17.0WB
18.0WB
19.0WB
24.0DB
225.0DB
226.0DB
26.0DB
27.0DB
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
012
5
24
14
9470
7410
10260
7480
10260
8050
11040
7540
11040
8090
30
22
10050
7630
10890
7730
10890
8290
11720
7820
11720
8370
36
33
10470
7730
11340
7910
11340
8470
12210
8000
12210
8560
42
45
10770
7900
11680
8020
11680
8580
12570
8140
12570
8690
6
24
14
8680
7060
9470
7140
9470
7700
10260
7210
10260
7760
30
22
9210
7230
10050
73440
10050
7900
10890
7440
10890
8010
36
33
9590
7350
10470
7480
10470
8020
11340
7590
11340
8130
42
45
9870
7420
10770
7570
10770
8120
11680
7700
11680
8230
7
24
14
7890
6710
8680
6800
8680
7360
9470
6870
9470
7420
30
22
8370
6830
9210
6950
9210
7500
10050
7060
10050
7590
36
33
8720
6900
9590
7050
9590
7580
10470
7180
10470
7710
42
45
8980
6950
9870
7120
9870
7650
10770
7270
10770
7780
8
24
14
7090
6370
7890
6470
7890
7020
8680
6550
8680
7080
30
22
7540
6420
8370
6560
8370
7090
7210
6680
9210
7200
36
33
7850
6450
8720
6620
8720
7140
9590
6770
9590
7280
42
45
8080
6470
8980
6650
8980
7180
9870
6830
9870
7330
9
24
14
6300
5980
7090
6140
7090
6690
7890
6230
7890
6760
30
22
6700
5990
7540
6160
7540
6750
8370
6300
8370
6820
36
33
6980
6010
7850
6180
7850
6790
8720
6350
8720
6840
42
45
7190
6040
8080
6190
8080
6830
8980
6370
89980
6860
10
24
14
5520
5520
6300
5710
6300
6190
7090
5920
7090
6380
30
22
5860
5580
6700
5730
6700
6220
7540
6000
7540
6400
36
33
6110
5610
6980
5770
6980
6270
7850
6050
7850
6420
42
45
6280
5740
7190
5820
7190
6300
8080
6090
8080
6440
014
5
27
18
10640
8330
11530
7400
11530
9050
12410
8470
12410
9090
33
27
11050
8350
11970
8500
11970
9110
12880
8600
12880
9200
39
39
11340
8370
12280
8560
12280
9170
13220
8660
13220
9270
45
52
11530
8460
12500
8580
12500
9180
13450
8710
13450
9300
6
27
18
9750
7900
10640
8020
10640
8650
11530
8100
11530
8720
33
27
11050
8350
11970
8500
1190
9110
12880
8600
12880
9200
39
39
11340
8370
12280
8560
12280
9170
13220
8660
13220
9270
45
52
11530
8460
12500
8580
12500
9180
13450
8710
13450
9300
7
27
18
8870
7360
9760
7540
9760
8100
10650
7720
10650
8240
33
27
9200
7400
10120
7580
10120
8140
11040
7760
11040
8280
39
39
9440
7420
10380
7600
10380
8170
11330
7770
11330
8310
45
52
9620
7440
10570
7620
10570
8190
11530
7780
11530
8330
8
27
18
7970
6810
8870
7020
8870
7580
9860
7230
9860
7760
33
27
8290
6870
9200
7060
9200
7600
10120
7250
10120
7800
39
39
8500
6900
9440
7090
9440
7630
10380
7290
10380
7820
45
52
8650
6920
9610
7110
9610
7680
10560
7310
10560
7840
9
27
18
7080
6300
7970
6500
7970
7060
8870
6730
8870
7250
33
27
7370
6250
8290
6570
8290
7110
9200
6770
9200
7300
39
39
7560
6380
8500
6600
8500
7140
9440
6800
9440
7320
45
52
7700
6410
8650
6630
8650
7170
9620
6830
9620
7350
10
27
18
6200
5800
7080
6010
7080
6400
7970
6280
7970
6760
33
27
6450
5840
7370
6050
7370
6630
8300
6300
8300
6800
39
39
6620
5850
7560
6100
7560
6630
8500
6330
8500
6830
45
52
6730
5860
7710
6120
7710
6640
8660
6350
8660
6840

Note:
1. DB - Dry bulb temperature ° C, WB - wet bulb temperature ° C.
 
2. The displayed cooling capacities in above chart are those at high-speed. Cooling capacities at medium speed and low speed should be values in above chart multiplied by the speed correction factors VS. 
 
 
12

 

Performance Data

Cooling Capacity
(W)   
Type
Inlet
Water
Temp
°C
 
Water
Volume
l/min
 
Water
Pressure
Drop
kPa
 
Inlet Air Temp
19.5WB
20.0WB
28.0DB
22.0WB
27.0DB
21.0WB
27.0DB
26.0DB
27.0DB
30.0DB
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
012
5
24
14
11430
7840
11830
7590
11830
8130
12620
7630
12620
8150
13410
8160
30
22
12140
8183
12560
7890
12560
8420
13400
8070
13400
8070
14240
8500
36
33
12640
8330
13080
8090
13080
8630
13960
8160
13960
8690
14830
8730
42
45
13010
8470
13470
8230
13470
8770
14360
8320
14360
8840
15260
8900
6
24
14
10640
7500
11040
7270
11040
7790
11830
7320
11830
7830
12620
7840
30
22
11300
7750
11720
7510
11720
8050
12560
7580
12560
8090
13400
8140
36
33
11770
7910
12210
7690
12210
8220
13080
7770
13080
8290
13960
8340
42
45
12120
8020
12570
7820
12570
8340
13470
7910
13470
8420
14360
8490
7
24
14
9860
7180
10260
6830
10260
7470
11040
6990
11040
7500
11830
7540
30
22
10470
7370
10890
7150
10890
7680
11720
7220
11720
7730
12560
7780
36
33
10900
7500
11340
7290
113470
7800
12210
7390
12210
7890
13080
7950
42
45
11220
7580
11680
7400
11680
7900
12570
7500
12570
8000
113470
8080
8
24
14
9070
6850
9470
6630
9470
7140
10260
6690
10260
7190
11040
7200
30
22
9630
6990
10050
6780
10050
7290
10890
6870
10890
7670
11720
7430
36
33
10030
7080
10470
6880
10470
7400
11340
7000
11340
7570
12570
7680
42
45
10330
7150
10770
6970
10770
7470
11680
7090
11680
7570
12570
7680
9
24
17
8280
6540
8680
6320
8680
6830
9470
6370
9470
6870
10260
6920
30
22
8790
6620
9210
6420
9210
6920
10050
6510
10050
7000
10890
7070
36
33
9150
6660
9590
6490
9590
6980
10470
6610
10470
7090
11340
7190
42
45
9430
6700
9870
6540
9870
7010
10770
6680
10770
7150
11670
7260
10
24
14
7490
6220
8790
6000
8790
6510
8680
6070
8680
6570
9470
6620
30
22
7950
6230
8370
6050
8370
6540
9210
6150
9210
6640
10050
6720
36
33
8280
6250
8720
6080
8720
6560
9590
6220
9590
6690
10470
6790
42
45
8520
6250
8980
6110
8980
6570
9870
6260
9870
6720
10770
6850
014
5
27
18
12850
8810
13300
8530
13300
9140
14180
8580
14180
9160
15070
9170
33
27
16650
9000
13810
8670
13810
9260
14730
8650
14730
9310
15660
9340
39
39
13690
9020
14160
8760
14160
9340
15120
8830
15120
9410
16060
9450
45
52
13930
9060
14420
8810
14420
9390
15370
8900
15370
9460
16340
9530
6
27
18
11960
8430
12400
8170
12400
8750
13290
8220
13290
8800
14180
8810
33
27
12400
8500
12860
8240
12860
8830
13780
8310
13780
8870
14700
8930
39
39
12740
8560
13210
8320
13210
8890
14150
7410
14150
8940
15110
9020
45
52
12980
8590
13460
8370
13460
8930
14420
8470
14420
9010
15370
9090
7
27
18
11090
8070
11540
7680
11540
8400
12410
7860
12410
8430
13300
8480
33
27
11510
8100
11970
7860
11970
8430
12880
7930
12880
8490
13900
8550
39
39
11800
8110
12270
7890
12270
8440
13210
8000
13210
8540
14160
8900
45
52
12020
8120
12510
7920
12510
8460
13460
8030
13460
8570
14430
8650
8
27
18
10200
78570
10650
7400
10650
7930
11530
7520
11530
8020
12410
8100
33
27
10590
7600
11050
7420
11050
7960
11970
7550
11970
8050
12880
8170
39
39
10860
7630
11330
7440
11330
7980
12270
7570
12270
8080
13210
8210
45
52
11060
7650
11530
7460
11530
8000
12500
7590
12500
8100
13450
8220
9
27
18
9310
7100
9260
650
9260
7420
10650
7100
10650
7560
11530
7700
33
27
9670
7120
10130
66980
10130
7460
11050
7130
11050
7600
11980
7740
39
39
9910
7150
10380
7000
10380
7480
11340
7150
11340
7640
12280
7760
45
52
10100
7180
10570
7010
10570
7510
11530
7160
11530
7660
12510
7780
10
27
18
8420
6600
8870
6470
8870
6960
9750
6630
9750
7130
10640
7380
33
27
8750
6650
9210
6500
9210
7000
10130
6670
10130
7150
11060
7300
39
39
8970
6680
9450
6530
9450
7020
10390
6700
10390
7180
11340
7330
45
52
9130
6700
9620
6550
9620
7040
10580
6710
10580
7200
11540
7340

Speed correction factor VS

Type
Medium Speed
Low Speed
Total Heat
Sensible Heat
Total Heat
Sensible Heat
012
0.89
0.87
0.73
0.69
014
0.89
0.87
0.73
0.69

 
13

 

Performance Data

Heat Capacity
(W)   

Type
Water
Volume
l/min
Water
Pressure
Drop
kPa
Inlet Air Temp
Inlet Water Temp
21.0DB
40
45
50
55
60
65
70
78
80
002
4
5
1490
1880
2280
2660
3060
3450
3850
4230
4630
5.5
8
1580
2000
2420
2840
3260
3680
4090
4510
4930
7
13
1650
2080
2520
2950
3400
3830
4260
4700
5130
8.5
17
1700
2150
2590
3050
3490
3940
4380
4840
5280
003
6
10
2150
2720
3280
3850
4420
4990
5550
6120
6680
8
17
2270
2860
3450
4060
4650
4250
5850
6440
7040
10
26
2350
2970
3580
4200
4810
5430
6060
6680
7290
12
34
1410
3050
3680
4310
4940
5580
6210
6840
7480
004
8
13
2920
3690
4470
5230
6000
6770
7540
8300
9080
11
18
3120
3930
4760
5570
6400
7220
8040
8860
9680
14
20
3240
4110
4970
5820
6680
7520
8390
9230
10090
17
31
3350
4230
5120
6000
6870
7760
8640
9520
10410
006
12
18
4080
5150
6230
7300
8390
9460
10530
11610
12680
15
27
4240
5370
6490
7600
8720
9840
10960
12070
13200
18
37
4370
5520
6680
7830
8980
10130
11280
12430
13600
21
57
4480
5650
6840
8010
9190
10360
11550
12720
13900
008
16
20
5900
7450
9000
10560
12110
13670
15210
16770
18320
22
36
6230
7870
9150
11150
12790
14430
16070
17710
19350
28
55
6450
8160
9860
11560
13260
14960
16670
18360
20060
34
79
6630
8370
10110
11860
13610
15350
17100
18840
20590
010
19
28
7000
8840
10080
12540
14380
16230
18060
19910
21750
25
45
7070
8940
10390
12670
14530
16390
18260
20120
21980
31
67
7140
9030
10910
12790
14680
16560
18450
20320
22200
37
90
7210
9100
11000
12900
14800
16700
18600
20500
22400
012
24
14
8220
10390
12550
14710
16860
19030
21190
23350
25520
30
22
8500
10730
12970
15210
17450
19680
21920
24160
26390
36
33
8710
11000
13290
15580
17880
20170
22460
24760
27050
42
45
8870
11210
13550
15890
18220
20560
22890
25260
27560
014
27
18
9240
11680
14110
16540
18960
21400
23830
26260
28710
33
27
9350
11800
14260
16730
19190
21400
24110
26570
29020
39
39
9430
11910
14390
16870
19370
21850
24330
26820
29300
45
52
9600
12140
14670
17210
19730
22270
24890
28360
29850
 
 
14

 

Performance Data

Heating Capacity

The displayed heating capacities in above chart are those at high-speed when inlet air dry-bulb temperature at 21°C DB. Heating capacities at medium speed and low speed should be values in above chart multiplied by the speed correction factors VS.
When inlet air dry-bulb temperature at 21°C, heat capacity correction methods are as follow:
Given that:
Air conditioner type
006
Water volume
18 l/min
Inlet water temp
60°C
Inlet air temp
18°C DB

Solution: look-up the chart: take model 006 as example, when inlet water temperature is 60° C, water flow 18 l / min, inlet air temperature 21°C, the heating capacity is 8980W:
Every difference of 1°C, its heating capacity variation is:
8980/(60-21 ) =230W/°C
When inlet air temperature is at 18°C, modified heating capacity is:
230X (60-18) = 9660W

Speed correction factor VS
Type
Medium
Speed
Low
Speed
002
0.84
0.72
003
0.85
0.73
004
0.86
0.74
006
0.87
0.75
008
0.86
0.74
010
0.86
0.74
012
0.87
0.75
014
0.87
0.75
 
 
15

 

Purchase Guideline

When select cooling unit is to match designed warm-up load with sensible heat load. In most cases, the coil has enough latent heat capacity, which can meet the design requirements. If air is used, the corresponding calculation formula should be changed:

 
Total heat capacity (W) x 0.86
 
Water temp rise (°C) =
60 X water flow (l/min)
 
     
 
Sensible heat capacity (W) x 0.86
 
Air temp rise (°C DB) =
0.29 X air flow (m3/h)
 

Choose according to air conditioner fan at high speed (cooling)
Fan coil unit is often selected according to air conditioner fan at high speed for the smallest unit type.
1. Determine working requirements (see selection guide)
Given that: indoor sensible heat cooling load
2330W
Inlet air temp
27°C DB, 19.5°C WB
Air flow
660m3/h
Total indoor heat cooling load
3140W
Inlet water temp
7°C
2. Determine unit specification, water volume and pressure drop
 
 
Check cooling capacity indicator when inlet air temp at 19.5°C WB, inlet water temp at 7°C WB. The sensible heat capacity should be the same or above the value needed. For the 004 type, it reads warm-up heat cooling load 2510W, total heat and cooling load of 3310W, water flow 8 l / min and the water pressure drop 13kPa. Cooling capacities at other speeds can be obtained by the speed correction factor Vs. Vs value should be checked in the chart of cooling capacity.

Choose according to air conditioner fan at medium speed (cooling)
The units usually operate at medium or low speed. So units can be selected under condition of average cooling load at medium speed.  And it permits to run at high speed with unusual or peak load to increase unit capacity.
1. Determine working requirements
Given that:
Average designed indoor sensible heat cooling load 
2330W
Inlet air temp
27°C DB, 19.5°C WB
Average designed air flow
340m3/h
Average designed indoor total heat cooling load
3140W.
Inlet water temp
7°C
2. Testing unit specifications
 
 
According to technical data sheet, medium speed air flow is 350m3/h, which is the closest to the required air volume in calculation. So 003 is selected.
 
 
16

 

Purchase Guideline

 
3.
According to cooling capacity correction sheet, find cooling capacity correction factor with test unit running at medium speed.
 Type 003 unit, multiplied by 0.84 with sensible heat capacity, or multiplied by 0.86 with total heat capacity.
 
4.
In order to determine modified sensible heat capacity and total heat, we use correction factor to divide average designed cooling load.

1480
 
=1760(W)(modified sensible heat load) 0.84
0.84
  

1980
 
=2302 (W)(modified total heat load)
0.86
  

5. Finally, determine water flow and pressure drop.
 
Use above modified load instead of the given load, at 27°C DB, 19.5°C WB and 7°C water temperature, to check cooling capacity performance chart.  The sensible heat and total heat load of selected unit should be the same or above modified load. According to the chart, for type 003, it reads that sensible heat is 1860W, total heat 2490W, water flow 6 l / min, pressure drop 10 kPa.

Heating (units selected by cooling function)
Units selected by cooling function are sufficient for heating. Heating capacity is determined when water flow is at the same level.  That is to use inlet water temperature to meet the indoor heating load.
1. Determine working requirements
Given that: type selected according to cooling load
Type 004
Indoor heating load
5820W
Water flow
8 l/min
Inlet water temp
21℃ DB

2. Determine water temperature needed
 
 
Check hot water heating performance chart, the 8 l/min inlet water temperature of 004 type unit is 60°C when air conditioner fan runs at high speed with heating capacity of 6000W.
 
 
17

 

Fan Performance

Standard Unit


High Static Pressure Unit


The technical data in this chart is measured when the unit runs at high speed in dry air with air filter and air return grille uninstalled.

 
18

 

Electrical Data

Electrical Wiring Diagram


 
Total unit consumption power (motor input power)

Type Specification
002
003
004
006
008
010
012
Power
(W)
VL/CL/VM
31
35
50
87
100
160
174
VP
35
77
87
134
174
210
268
Electric Current
(A)
VL/CL/VM
0.14
0.16
0.23
0.42
0.47
0.76
0.83
VP
0.16
0.34
0.42
0.60
0.84
1.00
1.25
 
Unit Output Power

Type Specification
002
003
004
006
008
010
012
Power
(W)
VL/CL/VM
8
12
16
40
16x2
40 X 2
40 X 2
VP
12
28
40
53
40 X 2
53 X 2
53 X 2
 
Note: The above is the data with high motor speed.

 
19

 

Noise Test


Test environment is an anechoic chamber with background noise less than 50db (A).

Supply Line

Type Specification
42CL, VM, Vp
42VL
002
003
004
006
008
010
012
002
003
004
006
008
010
012
Units
Air Filter
Speed Adjusting Switch
Temperature control switch
             
 
Note:
○Accessories with unit.
● Optional accessories. Orders for optional accessories should be indicated in purchasing contract.

 
20

 

Installation and Maintenance Instructions
 
1. Scope of Application
 
The unit uses50HZ/220VAC power, with ambient temperature of-30°C—+65°C,altitude not exceeding 4000m.
 
2. Unit Installation
 
Crouching units should be kept at horizontal level and vertical unit level should be adjusted by adjusting the bolts. Checkpoints for repairments should be considered when concealed type units are installed. Installed units should be covered against dust in process of renovation or decoration.
 
Pipeline Configuration and Anti-frost Measures
 
When install outlet water pipes, pipe clamp should be used to hold pipe end tightly. Valves should be installed on inlet and outlet water pipes. The highest point of the pipeline should be installed air release valve, the lowest point water release valve.
 
Condensation water requires a slope for successful discharge.
 
Strict anti-dew measures should be taken at valves of inlet and outlet water pipes and condensing water pipes.
 
4. Electrical Connection
 
In strict accordance with wiring diagram on the unit Note: Middle power line must be connected to the yellow line shown in the diagram. Grounding bolt inside the terminal box of unit is used for grounding connection protection system.
 
Do not put two or more (including two) units in connection in parallel; otherwise it will affect loop current in normal operation of the unit. Motor may be damaged.
 
Motor shaft bearing uses enclosed ball bearing motor, free from lubricant.
 
5. Water Supply Requirements
 
Prohibit the use of steam and hot water above 100 ° C. For double tube unit, hot water temperature should not exceed 65 ° C. If water above 65 ° C is used, softened water must be used; otherwise it will affect heat transfer effects because of corrosion.
 
Maximum water flows of all types of units do not exceed sample range. Water must be clean.
 
6. Anti-freezing Measures
 
If stop the operation of circulation pumps when the external temperature is below 0 ° C, the water in pipeline will freeze, causing cracks of coil units and pipe. So following measures must be taken:
 
1)
Continuous operation of circulation pump:
 
2)
Input antifreeze solution with appropriate concentration:
 
7. Maintenance
 
When start unit, first turn on air release valve to remove air and turn off air release valve when there is water flowing out.
 
The filter should be cleaned once a month or so. For coil unit, clean it periodically to ensure heat exchange efficiency.

 
21

 

Carrier, as a world-class manufacturer, takes following six responsibilities for environment protection:

   
   
 
Welcome to visit Carrier website
 
www.carrier.com.cn
   
  
 
 
Carrier China Sales Offices
Shanghai86-21) 2306 3000
Beijing86-10) 6583 2008
Guangzhou86-20) 3820 1818
Suzhou86-512)6511 0233
Chongqing86-23)6382 4732
Xi'an86-29)8762 0258
 
Carrier China Service Center
Service Hotline86) 800-820-2969/79
(86) 400-820-2969/79
 
Carrier China“Totaline”Spare Parts Business
Spare Parts Inquiry86)800-820-6010
 
 
In order to meet customers in a better way with our product improvements and innovations, we reserve the modifying rights to samples without prior notice
All rights reserved. Carrier China