EX-4.8.49 51 v238013ex4-8_49.htm SQX SERIES Unassociated Document
Exhibit 4.8.49 - Self-Control Components - SQX Series

4573                            
 
SQS35...      
SQS65...      
SQS85...      
 
Electrically Operated Valve Actuator
 
Stroke 5.5mm

 
     
SQS35.50, SQS35.53
 
SQS35.00, SQS35.03, SQS65, SQS65.2
SQS65.5
 
SQS85.00, SQS85.03
     
With spring-return/
 
without spring-return/
Without manual adjustment
 
with manual adjustment
Electrically Operated Valve (EOV)
l
SQS35…AC 220V working voltage, receiving three-position control signal
l
SQS85…AC 24V working voltage, receiving three-position control signal
l
SQS65…AC 24V working voltage, receiving DC 0…10V or DC 2…10V control signal
l
Adjustment power can reach 400N
l
0.5mm Stroke
l
Directly installing onto valve body without other facility
l
SQS35.00, SQS35.03, SQS85.00 and SQS85.03 have additional auxiliary switch function
l
meeting Standard of DIN 32 730, the actuator with/without spring return
l
Actuator without spring return has functions of manual adjustment and position display
l
Spring-return actuator with function of position display but without manual adjustment
Usage
Valve actuator is used for serial types of two-way valve, three-way valve, VVG44…,VVG45…,VVP45…, VMP43…, VMP44…, VMP45…, VXG44…, VXP45… and VV152…, and the drive stoke is 5.5mm.

Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003

 
 

 

l
Applicable area adheres to IEC 721-3-3 (Regulation 721-3-3 by International Electro-technical Commission ) Grade 3K5
l
Environmental temperature: -5…+50°C
l
Valve inner medium temperature: +2…+130°C
l
Using installation fittings ASK30 can drive the following 4mm or 5.5mm turn valves: X3i…, WG45…, VXG45…, VXG46… and VVI51…
Function Three-position or ratio control signal
Revisable synchro motor adopts three-way control signals (SQS35 and SQS85) or ratio control signal DC 0…10V (SQS65 and SQS65.5) or DC 2…10V (SQS65.2) for driving. It makes corresponding valve way through anti-lock gear mechanism.

Three-position control of Terminal Y1or Y2:
l
Y1 has voltage: valve rod contracts and valve gate opens
l
Y2 has voltage: valve rod extends and valve gate closes
l
Y1 or Y2 has no voltage: valve rod keeps in current position

SQS65…       Flow Characteristics Selection
Repositioning connection S1 (under cap/under print circuit board) can change the flow characteristics of 5.5mm turn valve (from “equal proportion” to “linear”). In any case, flow characteristics relate to valve way.
l
S1 connecting A and C can produce equal-proportion flow characteristics (factory set), which is mainly used for heating application.
l
S1 connecting B and C can produce linear flow characteristics, which is mainly used for cooling application.
l
For automatic operation, S1 connecting A and C or connecting B and C mainly depends on necessary flow characteristic.

S1 Position
   
S1 connect to: A & C
 
S1 connect to: B & C
(equal-proportion flow characteristics)
 
(Linear flow characteristics)
     
 

Flow Characteristics
Relationship between DC 0…10V or DC 2…10V control signal and volume flow control signal:
Y= DC 0…10V or DC 2…10V
R=0…1000Ω
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

Flow Characteristics
Log=equal=proportion valve characteristics (factory set)
Lin-linear valve characteristics
Flow range
K&100=volume flow 100%
K&=volume flow 0%

Volume flow


Type Overview
Type No.
Working
Voltage
Control Mode
(Control Signal)
Runtime
(Sec)
Spring-return
Function
Spring-return
Time(Sec)
SQS35.00
AC 230 V
Three-way
150
With
SQS35.03
35
SQS35.50
150
Without
8
SQS35.53
35
SQS65.5
AC 24 V
DC 0…10 V
35
with
8
SQS65
without
SQS65.2
DC 2…10 V
SQS85.00
Three-way
150
SQS85.03
35

Accessory
Name
Type No.
Applicative Actuator
Used Space
Auxiliary Switch
ASC9.6
SQS35.00,SQS35.03
SQS85.00,SQS85.03
1 x ASC9.6

Order
Please indicate quality, product name, type No. and accessory when ordering goods.
e.g.: 1 actuator, Type No. SQS35.00, 1 auxiliary switch, Type No. ASC9.6
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

Transportation
Actuator, valve and accessory are packed separately and not put together before dispatch.


Capability
The following 5.5mm return, thread two-way and three-way valve can be driven by electric actuators SQS35…, SQS65… and SQS85….
Type No.
DN[mm]
PN[Bar]
Technical Material
Two-way valve
VVG44…
VVP45…
VMP43…(2)
VMP44…(2)
VVG55…
VVI52…
15…40
10…20
15, 20
15, 20
15…25
15
16
16
16
16
25
25
N4364
N4845
N4841
N4844
N4379
N4377
Three-way valve
VXG44…
VXP45….
XMP43…
15…40
10…20
15, 20
16
16
16
N4464
N4845
N4841
Three-way valve with T bypass
VMP45…
VMP43…(4)
VMP44…(4)
10…20
15, 20
15, 20
16
16
16
N4845
N4841
N4844
Allowable pressure differentials of valve ΔPmax and ΔPa are listed in relevant valve technical material data sheet.

Machine Design
l
Electric actuator, maintenance free
l
Reversible synchro motor
l
Anti-lock gear mechanism
l
SQS35.50, SQS35.53 and SQS65.5 meet spring-return function of DIN 32730 Standard
l
Load switch is on stroke limit
l
Optional flow characteristics: It is equal-proportion or linear when SQS65… actuator connects valve type WG44…, VVI52… and VXG44…
l
Direct-pressure manual adjustment is used for all actuators without spring return: SQS35.00, SQS35.03, SQS65, SQS65.2 AND SQS85…
l
All actuators SQS35…, SQS65… AND SQS85… have position indicators
l
Auxiliary switch Type No. ASC9.6 applies to actuators SQS35.00, SQS35.03, SQS85.00 AND SQS85.03. Actuator Type No. SQS65.50 and SQS35.53 installs auxiliary switch witin the standard (not ASC9.6)
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

Manual Adjustment


SQS35.00, SQS35.03
 
SQS65, SQS65.2
 
SQS85…
 
1. 
Manual adjustment
 
2. 
Position indicator
 
3. 
Connecting bolt of valve neck

Terminal Strip and Auxiliary Switch, etc

 
     
SQS35…, SQS85…
 
SQS65…
     
5  terminal Strip
 
5  terminal Strip
     
6  auxiliary switch of SQS35.50 and
 
6  lin/logconnection
     
SQS35.53 within the standard
 
7  electrical bridge

Accessory
ASC9.6 auxiliary switch
 
Applying to actuators with Type No.SQS35.00, SQS35.03, SQS85.00 and SQS85.03
 
Switching point can be adjusted in the stroke range of 0…100%
 
Prefer “Technical Data” for accessory detail
   
Disposal
actuator must be splitted into constructional elements before disposal.

Project
Actuator must be install electrical connection according to local regulations and connection diagram
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

Notes:
It must adhere to regulations and requirements for personal and property safety at any time.
SQS65…
When using Actuator SQS65…, valves with Types VVG55…, VMP…, VVP… and VXP… must be connected onto “lin” for connectors of selected flow characteristics.
 
It must obey allowable temperature (see “Application” and “technical Data”). It must be illustrated in Facility Diagram if auxiliary switch is needed.

Installation
Direction


 
Valve Installation Handbook is printed on the back of actuator. Accessory Guide is put in corresponding accessory package box.
Debugging
Connection and function is inspected when debugging, in addition, auxiliary or auxiliary switch are also inspected and set necessarily.

   
Stroke0= valve door close
Stoke 1=valve door open

 
Manual Regulator: Manual regulator is rotated clockwise to close Siemens 5.5mm Stroke Valve (=0% stroke)
   
SQS35…/SQS85…
The flow characteristics of these actuators are linear when connecting to Valves of Type No. VVG44…, VVI52… or VXG444…
   
SQS65…
The flow characteristics of these actuators are equal-proportion (factory sets) by electrical assembly when connecting to Valves of Type No. VVG44…, VVI52… or VXG44…. The flow characteristics can turn to “linear” through relocating connectors.
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

Guarantee
Actuator Technical Date (Δpmax, ΔPs, leak rate, noise level and working life) apply to Siemens valves listed in matched “Compatibility” only.
 
Siemens neither guarantee nor promise if SQS… actuators are connected to third-party valve doors.
Maintain
When repairing valves: turn off pump and power source, turn off main stop valve on pipes, release pressure in pipes and cool it down completely. If necessary, electrical connection from terminal should be disconnected.
   
 
Actuator must be installed correctly with valve door, then restarting can be done.
 
Technical Data
 
Power Source
Working Voltage

SQS35…
AC230 V ± 15%, 50 / 60 Hz
SQS65…
AC 24 V ± 20%, 50 / 60 Hz
SQS85…
AC24 V ± 20%, 50 / 60 Hz

Power consumption

SQS35.00
2.5 VA
SQS35.03
3.5 VA
SQS35.50
5 VA
SQS35.53
6 VA
SQS65, SQS65.2
4.5 VA
SQS65.5
7 VA
SQS85.00
2 VA
SQS85.03
2 VA

Limiting converting volume of converting terminal 11 or 12
SQS35…, SQS85…
AC 250 V, 6A resistance/2.5A inductance

Working Parameter
   
Control Pattern (Control Signal)
   
SQS85…
 
three-position
SQS65, SQS65.5
 
DC 0…10V (in proportion)
SQS65.2
 
DC 210V (in proportion)
     
Runtime
 
On or Off
SQS35.00, SQS35.50, SQS85.00
 
50Hz, 150 s
SQS35.03, SQS35.53, SQS85.03
 
50Hz, 35 s
SQS65, SQS65.2, SQS65.5
 
50Hz, 35 s
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

Spring Return Characteristics
   
SQS35.50, SQS35.53, SQS65.5
 
turn-off time 8 s
Adjustment Force
 
400 N
Stroke
 
5.5 mm
     
Input Signal
   
Terminal Y (SQS65, SQS65.5)
 
DC 0…10V, Max 0.1 mA
Terminal Y (SQS65.2)
 
DC 2…10V, Max 0.1 mA
     
Terminal R (SQS65, SQS65.5, SQS65.2)
 
resistance 0…1000Ω
     
Output Signal
   
Terminal U (SQS65, SQS65.5, SQS65.2)
 
DC 0…10V, Max 0.5 mA
     
Enclosure Protection Standard
   
Enclosure Protection Standard
 
EN 60529, IP54
Cable bushing
 
Pg11 (2x)
Environment Condition
   
     
Valve inner medium temperature
 
+2…+130°C
     
Operation
 
IEC 721-3-3
Environmental Condition
 
Grade 3K5
     
Temperature
 
-5…+50°C
     
Humidity
 
5~95%rh
     
Transportation
 
IEC 721-2-3
Environmental Condition
 
Grade 2K3
     
Temperature
 
-25…+70°C
     
Humidity
 
<95%rh
     
Storage
 
IEC 721-1-3
Environmental Condition
 
Grade 1K3
     
Temperature
 
-5…+50°C
     
Humidity
 
5~95%rh
     
Industrial Standard
   
Meeting CE Authentication:
   
EMC directive
 
89/336/EEC
Low voltage directive
 
73/23/EEC
     
Size/Weight
   
Size
 
see “Size”
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

Weight
   
SQS35.00, SQS35.03, SQS65, SQS65.2
   
SQS85.00, SQS85.03
   
Packing not included
 
0.5kg
Packing included
 
0.6kg
     
SQS35.50, SQ35.53, SQS65.5
   
Packing not included
 
0.6kg
Packing included
 
0.7kg
     
Material
   
Actuator Shell
 
plastic
Luifel & manual regulator
 
plastic
Coupling wheel chain & lever
 
platic

Accessory
ASC9.6 auxiliary contact capacity of SQS35… and SQS85…
 
AC250V, 10A resistance/3A inductance


Connection Diagram
 
SQS35…
  
 
     
SQS35.00, SQS35.03
 
SQS35.50, SQS35.53
AC230V, three-position, no spring return
 
AC230V, three-position, spring return
     
Cm1 limit switch 100% stroke
 
c2 fixedly setting interior auxiliary switch
Cm2 limit switch 0% stroke
 
(factory installs, without ASC9.6 Accessory)
C1 linkable ASC9.6 auxiliary switch
   
L threading no-voltage terminal
   
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

SQS85…
 
 
SQS85.00, SQS85.03
 
AC 24V, three-position, no spring return

Cm1 limit switch 100% stroke
Cm2 limit switch 0% stroke
C1 installable ASC9.6 auxiliary switch
L threading no-voltage terminal

 
Connection Diagram
 
Connecting Terminal
 

G, G0
working voltage AC24 V
 
G    System Power line (SP), equivalent to LS on SQS56.2
 
G0  System null line (SN), equivalent to NS on SQS56.2

Input Signal
Y
SQS65, SQS65.5
DC 0…10 V
 
SQS65.2
DC 2…10 V
R
SQS65, SQS65.2, SQS65.50…1000 ohms
 
M
Detecting element
 
U Output Signal
 
 
SQS65, SQS65.2, SQS65.5
DC 0…10 V
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

All connection options are shown on connection diagram. Among these options, how many options and which option used depend on system situation.

Notes: If facility connects onto Terminal R, factory-setting electric bridge through R-M on print circuit board must be punctured.

SQS65, SQS65.5
 
(AC24 V, DC 0…10 V)


SQS65.2
 
(AC24 V, Dc 2…10 V)
 

Facility
F1
frost detector
K1 On/off Switch
K1
On/off Switch
N1 typical controller
N1
typical controller
P1 position indictor
P1
position indictor
R1 position converter
R1
position converter
Y1 Actuator
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003
 
 
 

 

Measurement     Unit of measurement: mm
 

*    Height after actuator installs on the valve
 
  > 100mm  minimum distance from wall to cover
 
>200mm used for places of installation, connection, operation or maintenance
 
Siemens Building Technologies
 
HVAC Products
CM1N4573C/03.2003