Exhibit 4.8.46 - Self-Control Components - Actuator - SKD 62
 
4563


Electro-hydraulically Operated Valve Actuator
SKD62
   
Stroke: 20mm
SKD60

l
SKD62…:
 
AC 24V operating voltage, DC 0…10V control signal
     
4…20mA or 0…1000Ω, with spring returning function
l
SKD60:
 
Same as SKD62, but without spring returning function
l
SKD62U:
 
Same as SKD62, but certified by UL
l
 SKD62UA:
 
Same as SKD62U, but functionality is improved (stroke limit control, sequence control of adjustable starting point and operating range and selection of operating direction)

l
Selection of linear or equally proportional flow characteristics
l
Valve position feedback
l
Stroke checking
l
Display of LED status
l
Compulsory control function
l
Designed with manual adjustment and position indicating functions
l
Regulating force up to 1000N
l
Directly installed onto valve body without adjustment
l
To improve the functionality by additional auxiliary switch, valve stem heating element and mechanical stroke inverter
l
SKD62U and SKD62UA certified by UL (American Appliance Quality Standard)
 
 
 

 
 
Application
Used for Siemens made series of two-way valve, three-way valve WF…, VVG…, VPF…, VXF…and VXG…, with a driving stroke of 20mm.
l
Field of application in accordance with IEC 721-3-3 (Provisions by   
International Electro-technical Commission 721-3-3) , Class 3K5
l
Ambient temperature: -15…+55℃
l
Temperature of medium flowing through the valve: -25…+140℃
 
 >140℃: Use SKB…actuators
 
 <0℃: Required to be used for heating element ASZ6.5 of the valve stem

Function
l
Electro-hydraulically actuator, maintenance free
l
Open the valve using pump, pressure cylinder and piston
l
Close the valve using spring return and by-pass valve
l
Designed with manual adjustment and position indicating function
l
SKD62…is designed with spring returning function, in accordance with DIN 32730
l
Standard electronic variant:
 
-
Selective control signal (DC 0 ... 10 V / 4 ... 20 mA / 0 ... 1000 Ω)
 
-
Selective flow characteristics (proportional / linear)
 
-
Valve position feedback
 
-
Stroke checking
 
-
Display of LED status
 
-
Compulsory control through terminal Z
l
SKD62UA variant with improved functionality:
 
-
Stroke limit control
 
-
Sequence control of adjustable starting point and Operating range
 
-
Selection of Operating direction (forward/reverse)
l
Installation space with auxiliary switch
l
Use valve stem heating element if necessary
l
Install mechanical stroke inverter if necessary (For SKB…only)
l
SKD62U and SKD62UA certified by UL (American Appliance Quality Standard)
 
 
 

 
 
Type

SKB…stroke 20mm
Model
Operating Voltage
Control
(Control Signal)
Spring Return
Function Time
Running Time
On    Off
Improved Functionality
Standard variant
SKD62
SKD62U*
AC 24V
DC 0…10V,
20mA  or
0…1000 Ω
Yes
15s
30s
15s
No
SKD60
No
-
Improved variant
SKD62UA*
AC24V
DC 0…10V,
4…20mA  or
0…1000 Ω
Yes
15s
30s
15s
Stroke limit control
Sequence control
Signal convariant
 
 
* Certified by UL
 
Accessories
Model
Description
ASC1.6
Auxiliary switch
ASZ6.5
Valve stem heating element AC 24V
ASK51
Mechanical stroke inverter

Placing an Order
Please indicate quantity, product name, model of the actuator when placing an order.
For example:
1 actuator, Model SKD62, and
 
1 auxiliary switch, Model ASC1.6.
Transportation
The actuator, valve and accessories are packed separately and are not assembled together during transportation.

Compatibility
Controller
The actuator can be driven by AC 24V SELV/PELV power supply and all the control systems running control signal of DC 0…10V or 4…20mA.
Installed on the linear valve
The actuator is used for the following Siemens made two-way valves and three-way valves, with a driving stroke of 20mm;
 
 
 

 
 
Valve
DN[mm]
PN[Bar]
Technical Literation
Two-way valve VV… (control valve or safety shut-off valve)
VVF21…(Flanged)
25…80
6
4310
VVF31…(Flanged)
25…80
10
4320
VVF40…(Flanged)
15…80
16
4330
VVF41…(Flanged)
50…50
16
4340
VVF45…(Flanged)
50…50
16
4363
VVF52…(Flanged)
15…40
25
4373
VVF61…(Flanged)
15…25
40
4382
Three-way valve VX… ( For control valve with functions of “confluence” and “split flow”)
VXF21…(Flanged)
25…80
6
4410
VXF31…(Flanged)
25…80
10
4420
VXF40…(Flanged)
15…80
16
4430
VXF41…(Flanged)
15…50
16
4440
VXF41…(Threaded)
15…50
16
4463
VXF61…(Flanged)
15 and 25
40
4482
Assembled valve VP…(integrated by two-way valve and pressure differential controller);
VPF52…(Flanged)
15…40
25
4374
 Refer to the valve technical data accordingly for permissible pressure differential
ΔPmax and OFF pressure differential ΔPa.

Note: Actuators with a stroke from 6mm through 20mm, can match with valves supplied by any third party as long as this party can provide materials to prove that their valves are of fail-safe mechanical design and can “shut off without applying voltage” and materials regarding required mechanical coupling.

For more information please contact your local Siemens office.
 
 
 

 

Technology
Principle of electro-hydraulically operated actuator
 
 
 
1.  Manual Regulator
2.  Pressure Cylinder
3.  Piston
4.  Oil Reservoir
5.  Pressure Chamber
6.  Pump
7.  Returning Spring
8.  By-pass Valve
9.  Coupler
10.Valve Rod
11.Inner Valve
12.Valve Positioner (0-1)
Closed
Opened
 
l
Signal input Y, increased voltage: pump (6) drives the hydraulic oil in the oil reservoir (4) to the pressure chamber (5), this action will produce a stroke: valve stem (10) contracts and valve head (11) opens.
l
Signal input Y, decreased voltage: by-pass valve (8) opens to allow the hydraulic oil return to the oil reservoir (4) from the pressure chamber (5) through returning spring (7), valve stem (10) extends and valve head (11) closes.
l
Signal input Y, constant voltage: the actuator and valve maintain at current stroke position.

Electronic diagram of SKD…actuators
 
 
 

 

Function of Spring Return
All SKD62…actuators are designed with spring return function in the factory. In case of power failure or lack of control signal, the spring may return to let the actuator return to the “0%” stroke position.
SKD60 actuators are not designed with spring return function. In case of power failure the actuator will stay at current stroke position.

Compulsory Control Function
There are three operating modes of the compulsory control input point (Z):
w/o such function
Compulsory control for 0…1000 Ω signal
 -     Disconnected Contact Z
 -     Valve stroke following control signal Y
 
 
 -   Z is connected to Contact M through resistor R
 -   Characteristics of linear or equally proportional flow
 -   Starting from 50 Ω / Ending at 900 Ω
 -   Point Y not to function
Fully opened valve
Fully closed valve
 
 -  Contact Z directly connecting to G
 -  Point Y not to work
 
 
 -   Z Contact directly connecting to G0
 -   Point Y not to work
 
Note: For Mode Z, assumption is made for setting of FORWARD in the factory.

Stroke Checking
Checking is required upon the first match between the valve and the actuator to determine the 0% and 100% stroke position of the valve. To this regard, mechanical connection is required between the valve and the actuator (See Section of Compatibility); the power supply is AC 24V. The checking process can be described repeatedly.
 
 
 

 

Prior to checking, make sure that the manual regulator is changed over “Auto” mode for recording an actual valve.
In order to commence the checking, the inside of the lockhole in the actuator’s typeplate must be short-circuited (for example, with screwdriver).
Auto checking procedures are as follows:

l Change the actuator over 0 stroke (Position (1)), the valve closes and the green LED light flashes.
l Then change the actuator over 100% stroke (Position (2)), the valve opens and the green LED light is ON.
l Save the measurements. The checking process ends. The green LED light is ON (Running normally).
l Change the actuator over positions controlled by control signal Y or Z(3).
l This process shows that Output Point U does not work, for example, the valve only act to represent the actual position when the green LED stops flickering or continues to keep shining
 

Display of LED Status
LED
Displays
Function
Correction
Green
ON
lOperate in normal
Running automatically, all in normal
 
Flickering
lIn process of stroke checking
Wait to end of checking
(LED stop flickering)
Red
 
ON
 
lStroke checking error
 
 
lInternal error
Check installation
Restart the checking process
(check holes by short circuiting)
Replace electronic elements
 
Flickering
lClogged internal valve
Check valves
    OFF
lNo power supply
lDefective electronic elements
Check the power supply
Replace electronic elements
 
 
 

 
 
 
Standard
Electronic
Variant
SKD62,
SKD60,
SKD62U
 
 
DIL Switch
   
 
ON
DC 4…20mA
Linear
 
*OFF
DC 0…10V
Equally proportional

 
Functionality
Improved
Electronic
Variant
SKD62UA
 
 
 
 
 
 
 
 
 
 

 
 
DIL Switch
       
ON
Reverse
Sequence control
DC 4…20mA
Linear
*OFF
Forward
Stroke limit control
DC 0…10V
Equally Proportional
* All the switches are set as OFF in the factory.
Selection of operating direction
l
For normally closed valves, FORWARD indicates an input signal of 0 V and valve closed (for all Siemens valves as listed in the Section “Compatibility” in Page 3).
l
For normally opened valves, FORWARD indicates an input signal of 0 V and valve opened.
Forward
Reverse
 
 
- input  DC 0…10V
             DC 4…20mA
             0…1000 Ω
 
- input   DC 10…0V
              DC 20…4mA
              1000…0 Ω
 
 
       
Note: function of mechanical spring return is unaffected by the operating direction.
 
 
 

 

Stroke limit control and sequence control
Setup Stroke Limit Control
 
Setup Sequence Control
Use the scroll switch LO and UP to adjust the stroke position up and/or down, with increased by 3% and a maximum of 45%
 
 
Use the scroll switch LO and UP to determine the starting point and the sequence within the operating range
 
LO Posi.   Min Stroke Limit
UP Posi.   Max Stroke Limit
LOPosi. Starting Point of Sequence Control
UP Posi.  Operating range of Sequence Control
0             0 %
0           100 %
0             0 V
0            10 V
1             3 %
1            97 %
1             1 V
1             3 V  *
2             6 %
2            94 %
2             2 V
2             3 V  *
3             9 %
3            91 %
3             3 V
3             3 V  *
4            12 %
4            88 %
4             4 V
4             4 V
5            15 %
5            85 %
5             5 V
5             5 V
6            18 %
6            82 %
6             6 V
6             6 V
7            21 %
7            79 %
7             7 V
7             7 V
8            24 %
8            76 %
8             8 V
8             8 V
9            27 %
9            73 %
9             9 V
9             9 V
A            30 %
A            70 %
A            10 V
A            10 V
B            33 %
B            67 %
B            11 V
B            11 V
C            36 %
C            64 %
C            12 V
C            12 V
D            39 %
D            61 %
D            13 V
D            13 V
E            42 %
E            58 %
E            14 V
E            14 V
F            45 %
F            55 %
F            15 V
F            15 V
*The minimum regulating variable is 3V;
 0…30V control is only for Y.

Accessories
Auxiliary Switch ASC1.6
- Switchpoint 0…5% stroke
 
Valve Stem Heating Element ASZ6.5
- Medium is below 0ºC
- Installed between the valve and the actuator
 

 
 
 

 
 
Engineering Precautions
Electrical connection of actuators must meet the requirements of local regulations and the wiring diagram in Page 11.
Strictly follow all the safety regulation and requirements to prevent from damage and injury.
Valve Stem Heating Element ASZ6.5 can generate a heat output of 30VA, and valve stem must avoid freezing when Operating in refrigerating range 0…-25. In this case, the actuator bracket and valve stem need not be insulated to ensure proper air circulation.
The body in contact with the non-insulated hot element may possibly be scalded.
Failing to follow the above-mentioned recommendations may possibly result in accidents or fire.
Follow the permissible temperature range (See Application and Technical Data).
 
 Instructions of Installation
Direction

 
Allowed
Not allowed
The guidelines of installation for assembling the valves and actuators can be found in the actuator packing box and the instruction manual of the accessories and the installing accessories can be found in the packing box.

Commissioning Precautions
During commissioning of system, you should check the cables and functions, set auxiliary switch, potentiometer and stroke limit device or check the setting values of existing parameters.
 
Cylinder with valve rod connectors contracts completely →stroke=0%
 
Cylinder with valve rod connectors projects completely →stroke=100%
The manual regulator must be rotated counterclockwise to the end, until the indicator marking red MAN disappears, to completely close the Siemens valve VVF…, VVG…, VPF…, VXF…and VXG…(stroke =0%).
 
 
 

 
 
 
Manual
Operation
 
Automatic Operation

Maintenance
When repairing valves:
l      Stop the pump and switch of the power supply. Close the main valves on the pipeline. Relieve pressure in the system. Cool the system down completely. If necessary, disconnect electrical wires and cables..
l      Commissioning must be made again when the valve can correctly be matched with the actuator.

Disposal
 
Actuators cannot be disposed as domestic wastes because they are provided with electronic and electrical components.
Disposal of actuator must comply with local laws, rules, and regulations.
 
Guarantee
Relevant technical dataPmax, ΔPs, leak rate, noise level and service life) regarding application are valid for Siemens actuators and valves listed in matched “Compatibility” only.
 
Matching of the actuator to valves from a third party must be approved by Siemens Building Technologies’ in prior; otherwise, all guarantees are in void.
 
 
 

 
 
Technical Data
Power supply
 
 
 
 
Operating Voltage (SELV, PELV)
AC 24V -20%
Frequency
50 or 60 Hz
Power Consumption
17 VA / 12 W
Fuse of Power Supply Cable
Min. 1 A
 
Max. 10 A
Operating Parameter
 
Type of Control (proportional)
DC 0…10 V, DC 4…20mA
 
or 0…1000 Ω
Running Time (50 Hz)
ON:30s / OFF:15s
Spring Returning Time (Closed)
15s
Standard Stroke
20mm
Regulating Force
1000 N
Flow Characteristics
Linear / Equally Proportional
 
Optional
 
Signal Input Point
Terminal Y
 Voltage
    Impedance Input
 Current
    Impedance Input
 Signal resolution
 Hysteresis phenomenon
 
DC 0…10 V
100 kΩ
DC 4…20mA
240Ω
< 1%
1%
Terminal Z
 Resistance
Compulsory control function
 Disconnected Z
 Z directly connected to G
 Z directly connected to G0
Z connected to M through 0…1000 Ω
 
0…1000 Ω
 
No (prioritized terminal Y)
Max. stroke 100%
Min. stroke 0%
Linear / Equally proportional
 Signal Output Point
Terminal Y
 Voltage
   Load impedance
 Current
   Load impedance
 
DC 0…9.8 V ±2 %
>500 Ω
DC 4…19.6 mA ±2 %
<500 Ω
 
 
 

 
 
General Ambient Conditions
Permissible highest operating temperature of valve inner medium
 
140 °C
Operation
Ambient conditions
Temperature
Humidity
Accord with IEC 721-3-3
Grade 3K5
15 ... +50 °C
5 ... 95 % rh
Transportation
Ambient conditions
Temperature
Humidity
Accord with IEC 721-3-2
Grade 2K3
30 ... +65 °C
<95 % rh
Storage
Ambient conditions
Temperature
Humidity
Accord with IEC 721-3-1
Grade 1K3
15 ... +50 °C
5 ... 95 % rh
Industrial Standard
In compliance with CE Standard
EMC directive
Low voltage protection directive
 
89/336/EEC
73/23/EEC
Electromagnetic Compatibility
Radiation interference
Immunity interference
 
EN 61000-6-3 (Residential)
EN 61000-6-2 (Industrial)
Electronic Auto Control Product Standard
EN 60 730-2-14
C-tick
N474
Protection Degree
EN 60529 IP54
Safety Degree
EN 60730 III
UL certification
UL 873
Dimensions
 
See “Dimensions”
Weight
SKB…
SKC…
ASK51 Stroke Inverter
3.60 kg (packaging included)
3.85 kg (packaging included)
1,10 kg (packaging included)
Material
Actuator case and bracket
Shell and manual regulator
Casting aluminum
Plastic
Piston-leading Cable
SKD62, SKD60
SKD62U, SKD62UA
Pg 11 (4 x)
Pg 16 (4 x)
Improved Functions SK…62UA
Forward / Reverse
DC 0...10 V / DC 10 ... 0 V
DC 4...20mA / DC 20 ... 4 mA
0 ... 1000 Ω / 1000 ... 0 Ω
Stroke Limit Control
Control lower limit range
Control upper limit range
0 ... 45 %, Adjustable
100 ... 55 %, Adjustable
Sequence Control
Terminal Y
Sequence staring point
Sequence operating range
 
0…15V, Adjustable
3…15V, Adjustable
Accessories
   
Auxiliary Switch ASC1.6
 
Convariant capacity
 
AC 24 V, 10 mA ... 4 (2) A
Valve Stem Heating Element ASZ6.5
Operating voltage
Power consumption (heat output)
AC 24 V ±20 %
30 VA
 
 
 

 
 
Wiring Diagram
 
 
 
 
 
 
 
 
 
 
B1 Sensor
F1 Temperature Limiter
N1 Controller
Y1 Actuator

Connection Terminals
 
G0: Operating voltage AC 24V  Neutral Line of the System (SN)
G: Operating voltage AC 24C  Earth Line of the System (SP)
Y: Control signal DC 0 ... 10 (30) V or DC 4 ... 20 mA
M: Neutral line of measurement (=G0)
U: Position display DC 0 ... 10 V or DC 4 ... 20 mA
Z: Compulsory input (See Functions in Page 5)

Auxiliary Switch ASC1.6
 
 
 

 
 
Dimensions
Dimensions in mm

*
Height of actuator without stroke inverter ASK51=300mm
 
Height of actuator with stroke inverter ASK51=357mm
**
Socket dia. of actuator SKD62U…corresponds to cable leading plug Pg16.
= >100 mm (minimum distance from the wall or ceiling).
▲▲
= >200 mm (for connection, operation or maintenance, etc.).
 
Stroke Inverter ASK50

* Max. stroke =20mm